General Safety Instructions
Technical Description
SSM-TEN072310
Page 11
3.11 Disconnection
The SSM-C must be disconnected for working at the SSM-C and at the SMU boards.
The device must be disconnected on both sides, i.e. the DC main lines to the SC via the
load-disconnecting switch, and the connected strings via the isolation terminals for PV
plus and PV minus. If there is no DC circuit breaker on the floor-mounted distribution
board, the DC fuses in the Sunny Central must be pulled in order to avoid reverse
voltage from the inverter.
Work carried out on the SMU board which, for example, involves unplugging the plug
connectors or removing the string fuses, is strictly only permissible under voltage-free
conditions.
WARNING!
If the isolation terminals are closed, the lower fuse holders are also energized
when the string fuse is disconnected!
The Plexiglas covers must always be mounted, to ensure protection against
accidental touching!
WARNING!
Before inserting the string fuses, the correct polarity and ground fault protection
must be ensured. The fuses may only be inserted or removed under load-free
conditions and using the appropriate personal protective equipment.
WARNING!
The isolation terminals may only be closed or opened under load-free
conditions.
WARNING!
Be careful of reverse voltage from the inverter!