Setting String Current Monitoring Parameters
Technical Description
SSM-TEN072310
Page 41
10 Setting String Current Monitoring Parameters
10.1 Triggering Time
The triggering time is the time between the first occurrence of a failure at a measuring
channel (deviation of string current outside the tolerance) and the display of a warning
at the SCC, with an assumed constant tolerance. The triggering time can also affect the
sensitivity of the string current monitoring system as it is included in the calculation of the
error sum. The triggering time is an adjustable value in the SCC, with a default setting
of 180 minutes.
"Device Set-up...SMUs...Parameters"
The triggering time can also be set directly in SDC as a parameter of the SCC.
[SMU Parameters]
Reg. SMUs
........3.SMUs
ErrorReportTime
........180 min Š