Installing the Floor-mounted Distribution Board
SMA
Technologie AG
Page 18
SSM-TEN072310
Technical Description
6 Installing the Floor-mounted Distribution Board
The SSM-C can be installed directly outdoors. Thus, the lengths of the DC string lines
can be minimized reducing the losses on the DC side.
In the case of a rack-mounted solar generator, the SSM-Cs can ideally be positioned
directly behind the generator in the shadow. Here, make sure that no rain flows over
the housing from the module surface.
The connection cables must be
routed into the housing's interior in a
sealed manner, in order to ensure
protection rating IP54.
Thus, it is also imperative to couple
the connection cables to the
integrated strain-relief clamp in the
base so that the weight of the
cables cannot exert any mechanical
strain on the housing. This also is
necessary for the IP54 protection
degree to be guaranteed.
NOTICE!
Ensure that no moisture is enclosed within the housing when installing the SSM-
C. An installation in rain or high air humidity can result in a failure or even
damage of the electronics in later operation!
NOTICE!
Select the installation location so that the SSM-C is protected from direct solar
radiation, and is freely accessible for maintenance work.