2 Safety
SMA Solar Technology AG
Quick Reference Guide
STP100-110-60-IS-xx-11
8
WARNING
Danger to life due to fire or explosion
In rare cases, an explosive gas mixture can be generated inside the product under fault
conditions. In this state, switching operations can cause a fire inside the product or explosion.
Death or lethal injuries due to hot or flying debris can result.
• In the event of a fault, do not perform any direct actions on the product.
• Ensure that unauthorized persons have no access to the product.
• Do not operate the DC load-break switch on the inverter in the event of ground fault
• Disconnect the PV array from the inverter via an external disconnection device. If there is no
disconnecting device present, wait until no more DC power is applied to the inverter.
• Disconnect the AC circuit breaker, or keep it disconnected in case it has already tripped,
and secure it against reconnection.
• Only perform work on the product (e.g., troubleshooting, repair work) when wearing
personal protective equipment for handling of hazardous substances (e.g., safety gloves,
eye and face protection, respiratory protection).
WARNING
Risk of injury due to toxic substances, gases and dusts.
In rare cases, damages to electronic components can result in the formation of toxic substances,
gases or dusts inside the product. Touching toxic substances and inhaling toxic gases and dusts
can cause skin irritation, burns or poisoning, trouble breathing and nausea.
• Only perform work on the product (e.g., troubleshooting, repair work) when wearing
personal protective equipment for handling of hazardous substances (e.g., safety gloves,
eye and face protection, respiratory protection).
• Ensure that unauthorized persons have no access to the product.
WARNING
Danger to life due to electric shock from destruction of the measuring device
due to overvoltage
Overvoltage can damage a measuring device and result in voltage being present in the
enclosure of the measuring device. Touching the live enclosure of the measuring device results in
death or lethal injuries due to electric shock.
• Only use measuring devices with a DC input voltage range of 1100 V or higher.
CAUTION
Risk of burns due to hot enclosure parts
The enclosure and the enclosure lid may get hot during operation. The DC load-break switch can
not become hot.
• Do not touch hot surfaces.
• Wait until the inverter has cooled down before touching the enclosure or enclosure lid.