3  Configuring Integrated Plant Control

Technical Information

IPC_STP-TI-en-14

9

Parameter Description 

3.3  Changing Inverter Operating Parameters

Always change operating parameters as described in this section. Some parameters that have sensitive functions can only 

be viewed and changed by qualified persons (for further information on changing parameters, refer to the manual of the 

communication product).
The operating parameters of the inverter are set to certain values by default. To optimize inverter operation, you can 

change the operating parameters using a communication product.

Requirements:

☐ Depending on the type of communication, a computer with a BLUETOOTH or Ethernet interface must be available.
☐ A communication product corresponding to the type of communication used must be available.
☐ The inverter must be registered in the communication product.
☐ The changes to the grid-relevant parameters must be approved by the responsible grid operator.
☐ For changing the grid-relevant parameters, the SMA Grid Guard code must be available (see "Application for SMA 

Grid Guard Code" at www.SMA-Solar.com).

Procedure:

1. Call up the user interface of the communication product or software and log in as 

Installer

 or 

User

.

2. If required, enter the SMA Grid Guard code.
3. Select and set the required parameter.
4. Save settings.

Parameter name for BLUETOOTH or 

Speedwire/Webconnect

Parameter name 

for RS485

Description

Rated apparent power of all inverters

Plnt.VARtg

Nominal apparent power of all inverters [kVA]

Ohmic resistance for impedance 

compensation

ImpCpn.OhmRis

Ohmic resistance for impedance compensation 

[ Ω ]

Inductive resistance for impedance 

compensation

ImpCpn.IndRis

Lagging resistance for impedance compensation 

[ Ω ]

Capacitive resistance for impedance 

compensation

ImpCpn.CapacRis

Leading resistance for impedance compensation 

[ Ω ]

Impedance compensation switched on

ImpCpn.IsOn

Impedance compensation switched on

/05*$&

Restricted function of Integrated Plant Control as a result of incorrect settings

If the required parameters for Integrated Plant Control are incorrectly calculated or if the parameters are entered 

incorrectly in the inverter, the functioning of Integrated Plant Control is restricted. SMA Solar Technology AG does not 

accept liability for incorrect entries made by customers. 

• For error-free functioning of Integrated Plant Control, the system must be modeled correctly using Sunny Design.
• If required, and subject to a fee, SMA Solar Technology AG can provide assistance with the correct calculation 

of the system parameters and with system parameterization.

Summary of Contents for STP 12000TL-US-10

Page 1: ...functions are available Device type Reactive power provision 0 overexcited to 0 underexcited Q on Demand 24 7 Integrated Plant Control STP 15000TL 10 STP 17000TL 10 from firmware version 2 60 02 from...

Page 2: ...er does not do any work and is therefore referred to as reactive power The time delay between the current and voltage curve its so called phase shift is a value which is easy to measure and characteri...

Page 3: ...n as pure reactive power Q unit Var from the French volt amp re r actif which moves back and forth in the cables Figure 2 Pure reactive power current and voltage are phase shifted by 90 1 3 Apparent P...

Page 4: ...compensated with Sunny Tripower inverters At the same time Sunny Tripower inverters can feed reactive power into the utility grid Compensation can take place both in feed in and non feed in operation...

Page 5: ...ansformers switching equipment etc has an influence on the characteristic curve of the PV power plant as a whole Figure 5 Example of a Q V specified by the grid operators This is why the central PV fa...

Page 6: ...ction point fast data transmission and installation and commissioning Grid friendly adherence to the characteristics desired by the grid operator even in the presence of very rapid changes in grid vol...

Page 7: ...length MV Transformer Nominal apparent power SN Impedance voltage vk Impedance loss in case of short circuit at nominal power Psc 3 2 Entering Key Values in Sunny Design You can find a detailed manua...

Page 8: ...rmer are activated in the area Configuration 10 Enter the key values for the cables used in the tabs Lines LV1 Lines LV2 and Lines LV3 11 In the tab MV transformer enter the key values for the MV tran...

Page 9: ...or software and log in as Installer or User 2 If required enter the SMA Grid Guard code 3 Select and set the required parameter 4 Save settings Parameter name for BLUETOOTH or Speedwire Webconnect Par...

Page 10: ...type and serial number PV system Impedance compensation Nominal apparent power of all inverters kVA Ohmic resistance for impedance compensation Lagging resistance for impedance compensation Leading r...

Page 11: ...ivate only the function Q on Demand 24 7 The general setting of the grid management service e g cos phi setpoint or Q V characteristic curve can be set independently of function Q on Demand 24 7 using...

Reviews: