4 Disconnecting the Inverter from Voltage Sources
SMA Solar Technology AG
Replacement Manual
STP50-4x-BFS-RM-xx-11
12
2. For STP 50-US-40 / STP 33-US-41 / STP 50-US-41 / STP 62-US-41: Set the AC load-break
switch of the inverter to position
O
.
3. Turn the DC load-break switch of the inverter to position
O
.
4. If the multifunction relay is used, switch off any supply voltage to the load.
5. Wait until the LEDs have gone out.
6. Use a current clamp to ensure that no current is present in the DC cables.
7. Note the position of the DC connector.
8.
DANGER
Danger to life due to electric shock when touching exposed DC
conductors or DC plug contacts if the DC connectors are damaged or
loose
The DC connectors can break or become damaged, become free of the DC cables, or no
longer be connected correctly if the DC connectors are released and disconnected
incorrectly. This can result in the DC conductors or DC plug contacts being exposed.
Touching live DC conductors or DC plug connectors will result in death or serious injury due
to electric shock.
• Wear insulated gloves and use insulated tools when working on the DC connectors.
• Ensure that the DC connectors are in perfect condition and that none of the DC
conductors or DC plug contacts are exposed.
• Carefully release and remove the DC connectors as described in the following.
9. For STP 50-40 / STP 50-41 / STP 50-JP-40 (use of
Sunclix DC connectors): Release and remove the
DC connectors. To do so, insert a flat-blade
screwdriver or an angled screwdriver (blade width:
3.5 mm) into one of the side slots and pull the DC
connectors out. When doing this, do not lever the
DC connectors out, but insert the tool into one of the
side slots only to release the locking mechanism. Do
not pull on the cable.
1
2
10. For STP 50-US-40 / STP 33-US-41 / STP 50-US-41 / STP 62-US-41 (use of Amphenol DC
connectors): Unlock the DC connectors using the corresponding unlocking tool and remove
(refer to the manufacturer manual for further information).
11. Ensure that the DC connectors on the product and those that are equipped with DC
conductors are in perfect condition and that none of the DC conductors or DC plug contacts
are exposed.
ENGLISH
Summary of Contents for STP 33-US-41
Page 57: ...1 SMA Solar Technology AG STP50 4x BFS RM xx 11 57 1 5 1 6 X703 1 X703 6 10...
Page 60: ...2 SMA Solar Technology AG STP50 4x BFS RM xx 11 60 DC DC DC DC 5...
Page 61: ...2 SMA Solar Technology AG STP50 4x BFS RM xx 11 61 AC DC DC AC DC 1000 V...
Page 62: ...2 SMA Solar Technology AG STP50 4x BFS RM xx 11 62 DC 5 C v v...
Page 67: ...5 BFS SMA Solar Technology AG STP50 4x BFS RM xx 11 67 5 DC DC DC 1 1 6 DC DC DC 7 8 X1...
Page 196: ...1 SMA Solar Technology AG STP50 4x BFS RM xx 11 196 1 5 1 6 X703 1 X703 6 10 WCtlHz Hz...
Page 198: ...2 SMA Solar Technology AG STP50 4x BFS RM xx 11 198 2 2 5 DC DC DC DC DC...
Page 199: ...2 SMA Solar Technology AG STP50 4x BFS RM xx 11 199 5 AC DC DC AC...
Page 200: ...2 SMA Solar Technology AG STP50 4x BFS RM xx 11 200 DC 1000 V DC 5 C...
Page 205: ...5 BFS SMA Solar Technology AG STP50 4x BFS RM xx 11 205 5 DC DC DC 1 1 6 DC DC DC 1 7 8 X1...
Page 211: ......
Page 212: ...www SMA Solar com...