11 Troubleshooting
SMA Solar Technology AG
Operating manual
STP3-6-3AV-40-BE-en-13
80
Event number
Message, cause and corrective measures
7102
Parameter file not found or defective
The parameter file was not found or is defective. The update failed. The in-
verter continues to feed in.
Corrective measures:
• Copy the parameter file to the correct folder again.
7105
Parameter setting failed
Parameters could not be set using the memory card. The inverter continues to
feed in.
Corrective measures:
• Ensure that the parameters are set correctly.
• Ensure that the SMA Grid Guard code is available.
7106
Update file defective
The update file is defective. The update failed. The inverter continues to feed
in.
7110
No update file found
No new update file was found on the SD memory card. The update failed.
The inverter continues to feed in.
7112
Update file successfully copied
7113
The memory card is full or write-protected
7201 to 7202
Data storage not possible
7303
Update main CPU failed
The cause must be determined by the Service.
Corrective measures:
• Contact the Service.
7320
The device was successfully updated
The firmware update was completed successfully.
7330
Condition test failed
The testing of the update conditions was successful. The firmware update
package is suitable for this inverter.
7331
Update transport started
Update file is being copied.