Technical data
SMA America, LLC
64
SB8-10TL-IUS103811
Installation Guide
12.3 Sunny Boy 10000TL-US
PV generator connection data
Grid connection data
Protection Devices
Equipment
Maximum DC power
10,350 W
Maximum array input power (DC@STC)
12,500 W
Maximum DC voltage
600 V
Peak power track voltage
300 V ... 480 V
Maximum DC input current
35 A
Number of MPP-Trackers
1 (OptiTrac)
Nominal AC power
10,000 W
Maximum AC power
10,000 W
Reduced power output at 140 °F (60 °C)
8,000 W
Maximum AC current
48 A
Nominal AC voltage
208 V
Nominal AC voltage range
183 V ... 229 V
Nominal AC frequency
60 Hz
Nominal AC frequency range
59.3 Hz ... 60.5 Hz
Power factor
1 at Nominal Power
Current THD
< 4 %
AC connection/power balancing
Dual Phase/O
Ground fault monitoring (R-Iso)
yes
DC reverse polarity protection
yes, short circuit diode
AC short circuit protection
yes, software controlled
AC overcurrent protection
yes, current controlled
Grid monitoring (SMA Grid Guard
®
2)
yes
DC connection
screw terminals
AC connection
screw terminals
LCD display
yes
Optional communication interfaces
RS485 or wireless (
Bluetooth
)