The resistance of the plus and minus pole and PE is measured each time before the
inverter starts feeding to the grid. If the resistance is below 2 M
Ω
the inverter does
not begin feeding the grid and the red warning LED goes on (see chapter 5:
‘Operation and Failure Indication LEDs’).
When the PV-panel is first connected to the Sunny Boy an electric
potential to protective earth arises on the plus and minus lines
equaling the PV-panel voltage (string voltage).
The monitoring of the isolation results in a minor electric connection be-
tween the plus, minus and PE. The high resistance of the monitoring cir-
cuit results in the fact that normally no danger arouses from this circuit,
even though certain voltage meters show a voltage between the case of
the inverter and the plus and minus pole.
A highly dangerous voltage is on between the plus and minus poles of the PV-panel
and PE also during grid feeding by the (transformerless) Sunny Boy 2000.