Always provide a sufficient connection of metal parts of the PV-panel
(metal frames, aluminum foil from the modules themselves, con-
struction holding the panels etc.) to the ground to allow that voltages
are discharged during operation.
The PV-panel may never be disconnected from the Sunny Boy (pull-
ing out the plug connectors) while under load, i.e. during the inverter
feeds to the grid. Always disconnect the mains first.
The plug connectors can be damaged by an electric arc occurring
when separating the PV-panel while feeding to the grid. In this case
both parts of the relevant plug connector have to be exchanged.
Caution: The input capacitors are still loaded even after disconnect-
ing the PV-panel from the inverter. Therefore the inverter still can
have high voltages for approx. 30 minutes even after disconnecting
the AC and DC side. The DC voltage can be up to 500 V. It is essen-
tial for qualified personnel to wait approx. 30 minutes after discon-
necting the device before opening it in order to let the harmful volt-
ages discharge.