Sunny Boy 2000
Technical Description
SB2000-11:EE
- 42 -
SMA Regelsysteme GmbH
Blinking code 2: Grid Failure
The yellow failure indication LED is activated for 5 seconds, is out for 3 seconds and
then blinks twice. The code is sent three times.
If the failure persists the indication blinking code is repeated.
The Sunny Boy is indicating a grid failure which has one of the following reasons:
•
Low grid voltage ( < V
AC min
•
High grid voltage ( > V
AC max
•
Low grid frequency (< f
AC min
•
High grid frequency ( > f
AC max
Check the electric grid supply (check the function of other electric consumers) and
check the fuse of the mains connector to the inverter.
If you do not detect any failure have the mains connection to the in-
verter checked by a qualified electrician.
This person should check the correct connection and the internal fuse
Disconnect the inverter before opening the device.