SMA
Technologie AG
Installation requirements
Installation Guide
SB2500-11:SE2006
Page 15
4.2 PV generator requirements
The Sunny Boy 2500 is designed to be connected to up to two strings (PV modules
wired in series) having a homogenous structure (modules of the same type, identical
orientation and tilt).
The „Sunny Design“ tool will help to dimension and check the size of your string with
respect to the inverter you intend to use. Information about the „Sunny Design“ tool
is available at www.SMA.de.
The unit has four DC plug connectors (two for each string) for connecting the PV
generators. The connecting cables from the PV generators must also be fitted with this
type of plug connector. A pre-assembled set for connecting the free cable ends from
a string is available as an optional accessory. The SMA order codes for the various
connectors are as follows:
• Multi-contact 3 mm: "SWR-MC"
• Multi-contact 4 mm: "MC-SET"
• Tyco:
"TYCO-SET"
4.3 Low voltage grid 230 V (AC)
The Sunny Boy must have a three-conductor connection to the mains (live (L), neutral
(N), protective earth (PE)).
The grid connection terminals on the AC connection
socket included in the accessories kit can take wires
with a cross-section of up to 2.5 mm². The accessories
kit also contains a PG13.5 AC connection socket for
connecting cables with a diameter between 9 mm and
13.5 mm, while the PG16 connection socket is used for
cables with a diameter up to a maximum of 17 mm. For detailed instructions, see
sections "Connecting the AC output with PG13.5" (page 22) and "Connecting the
AC plug with PG16" (page 24).
Limit values for DC input
Max. voltage
600 V (DC)
Max. input current
12 A (DC)
We recommend using a 16 A line circuit
breaker to protect the power circuit. No
loads should be connected to this power
circuit.
max. 2,5 mm²
9 … 17 mm
Cable
diameter
Wire cross-
section
Summary of Contents for SUNNY BOY 2500
Page 2: ......
Page 6: ...Table of Contents SMA Technologie AG Page 6 SB2500 11 SE2006 Installation Guide ...
Page 8: ...Foreword SMA Technologie AG Page 8 SB2500 11 SE2006 Installation Guide ...
Page 10: ...Safety information SMA Technologie AG Page 10 SB2500 11 SE2006 Installation Guide ...
Page 38: ...Replacing the varistors SMA Technologie AG Page 38 SB2500 11 SE2006 Installation Guide ...
Page 44: ...Contact SMA Technologie AG Page 44 SB2500 11 SE2006 Installation Guide ...
Page 45: ......