Installation requirements
Installation Guide
SB2500-11:SE2006
Page 17
The system impedance at the installation site of the Sunny Boy 2500 must be less than
1 Ohms for the islanding detection and the fuses to work porperly. In addition, we
recommend dimensioning the conductor cross-section so that line losses do not
exceed 1% at the nominal power. Line losses depending on the cable length and
cross-section are shown in the graph below.The compitation is based on copper
cables with several wires (phase and neutral).
Cable losses of the Sunny Boy 2500
The maximum cable lengths for the different cable cross-sections are as follows:
Conductor cross-section
1.5 mm²
2.5 mm²
Max. length
10 m
15 m
0.0%
0.2%
0.4%
0.6%
0.8%
1.0%
1.2%
1.4%
Length
0 m
10 m
15 m
20 m
25 m
30 m
35 m
40 m
45 m
50 m
5 m
Losses
1.5 mm²
2.5 mm²
Do not use cable specification with losses above 1.0 %