SMA
Technologie AG
Technical data
Installation Guide
SB2500-11:SE2006
Page 33
7.4 Sunny Boy 2500 Operating parameters
The parameters with a grey background are only visible when in installer mode.
Unauthorised changes to the operating parameters may result in:
• Injury or accidents as a result of changing the internal safety
routines in the Sunny Boy
• Voiding the Sunny Boy's operating approval certificate
• Voiding the Sunny Boy's guarantee
Never change the parameters of your Sunny Boy without express
authorization and instructions.
Name
Unit
Value range
Factory setting
Betriebsart /
Operating mode
MPP, IKonst, UKonst, Stopp,
Turbine Mode, Insel Mode
MPP
Default
GER/ENS
dFac-Max
Hz/s
0.005 ... 4.0
0,25
dZac-Max
mOhm
0 ... 20000
350
E_Total
kWh
0 ... 200000
Fac-Delta-
Hz
0 ... 4.5
0,19
Fac-Delta+
Hz
0 ... 4.5
0,19
h_Total
h
0 ... 200000
I-NiTest / Testcurrent Zac
mA
0 ... 8000
8000
Speicherfunktion /
Memory function
Default Parameter, Reset
Betriebsdaten, Reset Fehler
none
Speicher / Storage
Permanent, volatile
Permanent
T-Start
s
5 ... 300
10
T-Stop
s
1 ... 3600
2
Uac-Min / Vac-Min
V
180 ... 300
198
Uac-Max / Vac-Max
V
180 ... 300
260
Upv-Start / Vpv-Start
V
250 ... 600
300
Usoll-Konst / Vconst-Setpoint
V
250 ... 600
600
Summary of Contents for SUNNY BOY 2500
Page 2: ......
Page 6: ...Table of Contents SMA Technologie AG Page 6 SB2500 11 SE2006 Installation Guide ...
Page 8: ...Foreword SMA Technologie AG Page 8 SB2500 11 SE2006 Installation Guide ...
Page 10: ...Safety information SMA Technologie AG Page 10 SB2500 11 SE2006 Installation Guide ...
Page 38: ...Replacing the varistors SMA Technologie AG Page 38 SB2500 11 SE2006 Installation Guide ...
Page 44: ...Contact SMA Technologie AG Page 44 SB2500 11 SE2006 Installation Guide ...
Page 45: ......