SMA
Technologie AG
Rating for a line circuit breaker
Installation Guide
SB2500-11:SE2006
Page 41
Conclusion
The selected line circuit breaker cannot be used in our example case since the
maximum current-carrying capacity for fault-free operation is lower than the
maximum output current of the inverter used.
It will trip under rated operating
conditions!
In this case one solution would be to ensure there is an 8 mm gap between the circuit
breakers. This would mean that the reduction factor is 0.98 instead of 0.77. As a
result, the maximum current-carrying capacity would increase to 9.4 A.
As well as the thermal rating of the circuit breakers and all other factors as specified
in section "Rating for a line circuit breaker in a photovoltaic electrical power unit
operated in parallel with the low-voltage grid" (page 16), of course the applicable
standards
1
also need to be taken into account. The main ones that apply here are:
• DIN VDE 0100; part 410 and/or the international standard IEC 364-4-41:1992
• DIN VDE 0100; part 430 and/or the international standard IEC 364-4-43:1977
and IEC 364-4-473:1977
• DIN VDE 0298; part 4
In special applications the relevant standards must be followed.
1. The standards listed here are standards that apply to Germany. Please note
that other standards apply in other countries. Beside the standards above
other standards may be applicable in special installations.
Summary of Contents for SUNNY BOY 2500
Page 2: ......
Page 6: ...Table of Contents SMA Technologie AG Page 6 SB2500 11 SE2006 Installation Guide ...
Page 8: ...Foreword SMA Technologie AG Page 8 SB2500 11 SE2006 Installation Guide ...
Page 10: ...Safety information SMA Technologie AG Page 10 SB2500 11 SE2006 Installation Guide ...
Page 38: ...Replacing the varistors SMA Technologie AG Page 38 SB2500 11 SE2006 Installation Guide ...
Page 44: ...Contact SMA Technologie AG Page 44 SB2500 11 SE2006 Installation Guide ...
Page 45: ......