Rating for a line circuit breaker in a photovoltaic electrical
power unit operated in parallel with the low-voltage grid
Various factors should be taken into account when selecting line circuit breakers.
These include, for example:
• The type of cable used (conductor material and insulation)
• Ambient temperatures affect the cables (higher temperatures result in a reduced
maximum current load)
• Method of routing the cable (reduces the ampacity of the conductor)
• Bundling cables together (reduces the ampacity of the conductor)
• Loop impedance [Z] (in the event of a body contact this limits the current that can
flow and therefore determines the response behaviour of the circuit breaker)
• Adequate space between the line circuit breakers in order to avoid overheating
(in case of overheating, the line circuit breaker could trigger earlier).
• Selectivity
• Protection class of the connected load (VDE 0100, part 410), Protection against
electric shock and / or the international standard IEC 60364-4-41:1992
The following standards
1
should be followed in all cases:
• DIN VDE 0298-4
(„Types of cable installation and conducting
capacity“)
• DIN VDE 0100; part 430
(„Protection measures for protection of cables
and conductors in terms of overcurrent“) and
/ or the international standard IEC
364-4-43:1977 and IEC 364-4-473:1977
• DIN VDE 0100; part 410
(Protection against electric shock“) and / or
the international standard IEC 60364-4-
41:1992
Please have a look at chapter 9 "Rating for a line circuit breaker" (page 39).
1. The standards mentioned above are to be only used as a guideline for your
installation. They apply for installations in Germany. Please note that other
standards will apply for different countries throughout the world.
Summary of Contents for SUNNY BOY 2500
Page 2: ......
Page 6: ...Table of Contents SMA Technologie AG Page 6 SB2500 11 SE2006 Installation Guide ...
Page 8: ...Foreword SMA Technologie AG Page 8 SB2500 11 SE2006 Installation Guide ...
Page 10: ...Safety information SMA Technologie AG Page 10 SB2500 11 SE2006 Installation Guide ...
Page 38: ...Replacing the varistors SMA Technologie AG Page 38 SB2500 11 SE2006 Installation Guide ...
Page 44: ...Contact SMA Technologie AG Page 44 SB2500 11 SE2006 Installation Guide ...
Page 45: ......