Installation
SMA
Technologie AG
Page 24
SB2500-11:SE2006
Installation Guide
Connecting the AC plug with PG16
To connect a cable with a cross-section between 13.5 mm² and 16 mm², proceed as
follows.
1.
First of all, slide the pressure screw with the PG16 screw fitting onto the cable.
Now slide the threaded sleeve over the cable.
2.
Now connect the individual conductors to the socket element in sequence.
-
Protective earth PE (green/yellow) to the screw terminal
with the earth sign. It is required that the PE wire is
slightly longer than the L and N wires.
-
Neutral conductor N (blue) to screw terminal 1.
-
Live L (brown or black) to screw terminal 2.
-
Terminal 3 remains unused.
3.
Make sure the wires are securely connected.
4.
Now screw the threaded sleeve onto the socket element and tighten it.
Threaded sleeve
Pressure screw with
PG16 screw fitting
1
2
3
Terminals in the socket
element
Threaded sleeve
Socket element
Connected wires
Pressure screw with
PG16 screw fitting
Threaded sleeve
screwed onto socket
element
Pressure screw with
PG16 screw fitting