Installation
SMA
Technologie AG
18
SB40TL_50TL-IEN081211
Installation Guide
5.1.2 Ambient Conditions
•
The installation location and installation method must be suitable for the weight and
dimensions.
•
Install on a solid surface.
•
The installation location must be accessible at all times.
•
The ambient temperature should be below 40 °C at all times to guarantee optimal operation.
•
Do not expose the Sunny Boy to direct sunlight to avoid a power reduction due to excessive
heating.
•
In a living area, do not install the unit on plasterboard walls, etc., as
otherwise audible vibrations are likely to result.
The Sunny Boy can make noises which may be regarded as a nuisance
if it is installed in a living area.
5.1.3 Safety Clearances
Observe the following minimum clearances to walls, other devices or objects to guarantee sufficient
heat dissipation and enough space for pulling the Electronic Solar Switch handle.
Direction
Minimum clearance
Sides
10 cm
Top
30 cm
Underside
50 cm
Front
5 cm
Multiple Sunny Boys installed in areas with high ambient temperatures
If necessary, increase the clearance and ensure that the supply of cool air is sufficient to
cool the Sunny Boys.
Electronic
Solar
Switch