6.4 Setting the installation country
The Sunny Boy can be configured for multiple countries. This is done using two rotary switches in
the Sunny Boy or by configuring the "CntrySet" parameter using a communication device.
Switch position 0 / 0 is the setting on delivery. If you ordered the Sunny Boy with specific country
configurations, the settings were made in the factory using a communication device. These settings
are overwritten if the rotary switches or a communication device are used to make changes and
cannot be restored automatically. If the unit was ordered without specifying the installation country,
the standard setting is VDE0126-1-1 and the language is German.
Changes are saved immediately after the line circuit breaker is switched on. If an unassigned switch
position is selected, the Sunny Boy displays an error message.
Protected country data sets
The local grid connection regulations in some countries require a device which prevents the
parameters for grid feeding being changed. For this reason, some country data sets are protected.
Protected country data sets are automatically blocked 10 feed-in hours after commissioning or after
the last change. If the country data set is changed after these 10 feed-in hours, the Sunny Boy does
not accept the changes and displays the error message "Grid parameters locked". However, if a
retrospective change to the country data set only involves changing the display language, the
change is saved immediately.
The country data sets can also be set, manually locked or unlocked using a communication device
("CntrySet" parameter). The parameter "Inst.-Code" must be set to "54321" to lock the data set. It
can only be unlocked by entering a personal unlocking code and is valid for max. 10 feed-in hours.
The language can be set without a password regardless of the country data set.
Changing parameters in protected country data sets
If parameters are changed in protected country data sets, they are no longer protected
and "adjusted" is displayed instead of the standard. The parameter "Inst.-Code" must be
set to "54321" to lock the data set manually.
Switch 1
Switch 2
Summary of Contents for SUNNY BOY 4000TL
Page 6: ...SMA Technologie AG 6 SB40TL_50TL IEN081211 Installation Guide...
Page 16: ...Technical Data SMA Technologie AG 16 SB40TL_50TL IEN081211 Installation Guide Efficiency curve...
Page 73: ...SMA Technologie AG Contact Installation Guide SB40TL_50TL IEN081211 73...
Page 74: ...Contact SMA Technologie AG 74 SB40TL_50TL IEN081211 Installation Guide...