SMA Solar Technology AG
88
SB50US-80US-IUS094030
Installation Guide
Disturbance
Imax
Over current on the AC side. This failure code is
indicated in case the current to the AC grid
exceeds the specification. This may happen in
case of harmfull interference on the grid. If you
observe “Imax“ often, check your grid. For
assistance contact SMA.
Disturbance
K1-Close
Relay test failed. Contact SMA for assistance.
Error
K1-Open, K2-Open
Disturbance
MSD-FAC, MSD-Idif
Internal measurement comparison error: The
Sunny Boy measured values of BFR and SRR are
too different from each other.
Contact SMA for assistance.
Error
MSD-VAC
Disturbance
OFFSET
Grid monitoring self-test failed.
Error
ROM
The internal test of the Sunny Boy control system
firmware failed. Contact SMA in case you
observe this failure often.
Disturbance
Shut-Down
Internal over current continuous
Disturbance
Vac-Bfr, Vac-Srr
The AC grid voltage is exceeding the allowable
range. (“Bfr“ or “Srr“ is an internal message and
is not important for the user.) Vac can also result
from a disconnected grid or a disconnected AC
cable. The Sunny Boy assumes that the public
grid is down and disconnects from the grid in
order to avoid islanding.
If the grid voltage is within the tolerable range
and you still observe the failure message “Vac-
Bfr“ or “Vac-Srr“ contact SMA America.
Disturbance
VacL1-Bfr,
VacL2-Bfr,
VacL1-Srr,
VacL2-Srr
Voltage is too high or too low on the indicated
leg.
Disturbance
VpvMax
!PV Overvoltage!
!Disconnect DC!
DC input voltage above the tolerable maximum
value.
Disconnect DC immediately!
Disturbance
Watchdog
Watchdog for operation control triggered
Error Type
Error Code
Description