Technical data
Installation Guide
SB1100LV-11:SE2006
Page 41
8.4.2 Parameter settings for Germany
Grayed out parameters are only displayed in installer mode. The table below contains
the parameters that are applicable in Germany.
Name
Unit
Value range
Factory setting
ACVtgRPro
V
230 ... 300
253
AntiIsland-Ampl * grd
0 ... 10
0
AntiIsland-Freq * mHz
0 ... 2000
500
Default *
GER/VDE0126-
1-1, GB/G83,
SP/RD1663,
Off_Grid,
Other, trimmed
GER/VDE0126-1-1
dFac-Max *
Hz/s
0.1 ... 4.0
0.25
dZac-Max *
mOhm
0 ... 20000
750
E_Total
kWh
0 ... 200000
Fac-delta- *
Hz
0.1 ... 4.5
2.45
Fac-delta+ *
Hz
0.1 ... 4.5
0.19
h_Total
h
0 ... 200000
I-NiTest *
mA
0 ... 7500
6000
Operating mode
MPP, UKonst,
Stopp, Turbine
Mode, Off Grid
MPP
Storage function
Default
Parameter, Reset
Operating Data,
Reset Fault
None
Speicher/
Storage
Permanent,
volatile
Permanent
T-Start *
s
5 ... 300
10
T-Stop
s
1 ... 3600
2
Uac-Min *
V
160 ... 230
198
Uac-Max *
V
230 ... 300
260
Upv-Start
V
20 ... 60
25
Usoll-Konst
V
26 ... 63
63
Summary of Contents for Sunny Boy SB 1100LV
Page 2: ......
Page 8: ...Foreword SMA Technologie AG Page 8 SB1100LV 11 SE2006 Installation Guide ...
Page 10: ...Safety instructions SMA Technologie AG Page 10 SB1100LV 11 SE2006 Installation Guide ...
Page 32: ...Installation SMA Technologie AG Page 32 SB1100LV 11 SE2006 Installation Guide ...
Page 44: ...Technical data SMA Technologie AG Page 44 SB1100LV 11 SE2006 Installation Guide ...
Page 50: ...Replacing the varistors SMA Technologie AG Page 50 SB1100LV 11 SE2006 Installation Guide ...
Page 58: ...The communications interface SMA Technologie AG Page 58 SB1100LV 11 SE2006 Installation Guide ...
Page 61: ......