Rating for a Line Circuit Breaker in a Photovoltaic Power Generating
System Operated in Parallel to the Low Voltage Grid
Various factors should be taken into account when selecting line circuit breakers. These
include, for example:
•
The type of cable used (conductor material and insulation)
•
Ambient temperatures affecting the cables (higher temperatures result in a reduced
maximum current load)
•
Method of routing the cable (reduces the maximum current load)
•
Bundling cables together (reduces the maximum current load)
•
Loop impedance [Z] (in the event of a body contact this limits the current that can
flow and therefore determines the response behavior of the circuit breaker)
•
Sufficient distance between the circuit breakers so as to avoid undue heating (heat
can trigger the circuit breaker early)
•
Selectivity
•
Protection class of the connected load (VDE 0100, part 410), Protection against
electric shock
The following standards should be followed in all cases:
Please pay attention to section 10 "Rating for a Line Circuit Breaker" (Page 55).
•
DIN VDE 0298-4
(Cable routing and current-carrying capacity)
•
DIN VDE 0100, part 430
(Protective measures; protection of cable and
cords against overcurrent)
•
DIN VDE 0100, part 410
(Protective measures; protection against electric
shock)
Summary of Contents for Sunny Boy SB 2500
Page 2: ......
Page 6: ...Explanation of the Symbols Used SMA Technologie AG Page 6 SB25_30 11 SE0307 Installation Guide...
Page 10: ...Safety Instructions SMA Technologie AG Page 10 SB25_30 11 SE0307 Installation Guide...
Page 20: ...Installation Requirements SMA Technologie AG Page 20 SB25_30 11 SE0307 Installation Guide...
Page 62: ...The Communication Interface SMA Technologie AG Page 62 SB25_30 11 SE0307 Installation Guide...
Page 65: ......