Installation Requirements
Installation Guide
SB25_30-11:SE0307
Page 17
For optimum operation of the inverters, the grid impedance of the AC cable must not
exceed 1 Ohm. This is necessary, amongst other things, for the correct operation of the
impedance monitoring. In addition, we recommend dimensioning the cable cross-
section so that output losses do not exceed 1 % at nominal power. Output losses as a
function of cable length and cross-section are shown in the graphs below. Multi-wire
cables with copper forward and return conductors are used.
Output Losses of the Sunny Boy SB 2500
The maximum cable lengths for the different cable cross-sections are as follows:
Cable cross-section
1.5 mm²
2.5 mm²
Max. length
9 m
15.5 m
Do not use cables where losses will exceed 1.0 %
Cable length
Out
p
u
t lo
sse
s