SMA
Technologie AG
Technical Data
Installation Guide
SB25_30-11:SE0307
Page 45
8.4.2 Parameter Settings for Germany
The grayed-out parameters are only displayed in installer mode.
Warning!
Unauthorized changes to the operating parameters may result in:
•
injury or accidents as a result of changing the internal safety routines
in the Sunny Boy,
•
voiding the Sunny Boy's operating approval certificate,
•
voiding the Sunny Boy's warranty.
Never change the parameters of your Sunny Boy without express
authorization and instructions.
Name
Short
descr.
Value range
Factory setting
Sunny Boy
SB 2500
Sunny Boy
SB 3000
ACVtgRPro
V
230 ... 300
253
253
AntiIsland-
Ampl*
grd
0 ... 10
0
0
AntiIsland-Freq* mHz
0 ... 2000
500
500
Betriebsart
MPP,
Konstantspg.,
Stop, Turbine
MPP
MPP
Default *
GER/VDE0126-
1-1, GB/G83,
Off_Grid,
SP/RD1663,
Other, trimmed
GER/VDE0126-1-1 GER/VDE0126-1-1
dFac-MAX *
Hz/s
0.005 ... 4.0
4
4
dZac*
mOhm
0 ... 20000
700
700
E_Total
kWh
0 ... 200000
Fac-delta+ *
Hz
0 ... 4.5
0.19
0.19
Fac-delta- *
Hz
0 ... 4.5
2.45
2.45
h_Total
h
0 ... 200000
I-NiTest *
mA
0 ... 15000
8000
9000
Speicher/
Storage
permanent,
volatil
permanent
permanent
Summary of Contents for Sunny Boy SB 2500
Page 2: ......
Page 6: ...Explanation of the Symbols Used SMA Technologie AG Page 6 SB25_30 11 SE0307 Installation Guide...
Page 10: ...Safety Instructions SMA Technologie AG Page 10 SB25_30 11 SE0307 Installation Guide...
Page 20: ...Installation Requirements SMA Technologie AG Page 20 SB25_30 11 SE0307 Installation Guide...
Page 62: ...The Communication Interface SMA Technologie AG Page 62 SB25_30 11 SE0307 Installation Guide...
Page 65: ......