5-2
SMA America
SB700U-11:SE3207
Note:
If there is a ground fault in the array, the
„EarthCurrentMax“ error message will be displayed and the
GFDI fuse may clear. If this error message is encountered,
switch off the DC and AC disconnects to the Sunny Boy and
troubleshoot the array.
Note:
If the Sunny Boy is not operating as expected after
the commissioning procedure has been completed, refer to
Section 6: Displays and Messages and to Section 7:
Troubleshooting.
Note:
If there is adequate solar irradiation and the
resulting PV input voltage is sufficient, the Sunny Boy will
automatically begin feeding power to the utility grid.
Note:
The Sunny Boy operates from the power produced
by the PV array and is designed for minimal internal DC-
power consumption. The maximum power that the Sunny Boy
will consume in normal operation is 4 W.
Note:
Anytime the AC power is disconnected from the
inverter, either manually or as a result of an AC disturbance,
the inverter will wait 5 minutes after the AC power has been
restored to reconnect. When servicing the inverter, always
disconnect the DC first, then the AC.
Summary of Contents for Sunny Boy SB 700U
Page 1: ...Sunny Boy SB 700U Installation Guide Version 1 1 SB700U 11 SE3207 TBE SB07U...
Page 2: ...ii SMA America SB700U 11 SE3207...
Page 14: ...1 6 SMA America SB700U 11 SE3207...
Page 16: ...2 2 SMA AmericaSB700U 11 SE3207...
Page 24: ...3 8 SMA America SB700U 11 SE3207 11 Verify that the Sunny Boy 700U is firmly mounted in place...
Page 46: ...4 22 SMA America SB700U 11 SE3207...
Page 50: ...6 2 SMA America SB700U 11 SE3207 Figure 6 1 The Sunny Boy LED Status Indicator...
Page 84: ...8 6 SMA America SB700U 11 SE3207...
Page 85: ......