Memory Function
no function
default param.
reset Op.Data
Reset errors
No
function
Default param.: Sets all parameters to default.
Reset Op.Data: Sets all parameters that are
visible in user level to default values.
Reset errors: Resets all permanent device
disable (dBh) and the failure „EarthCurMax“
occurs. To remove this failure, follow the steps
in „Section 5: Commissioning the Sunny Boy“
Operating Mode
MPP-Operation
Turbine
V-const
Stop
MPP
Operating Mode of the Sunny Boy:
MPP-Operation: Maximum Power Point
Turbine: Operating mode for wind power
plants
V-const: Constant Voltage Mode (Setpoint
defined in „Vconst-Setval“)
Stop: Disconnection from utility, no operation
Pmax
W
0 ... 510
460
Maximum power output of the inverter
T-Start
s
5 ... 1600
10
The time the inverters waits to connect to the
grid after Vpv-Start is exceeded.
This value defaults to 5 minutes after a utility
fault.
T-Stop
s
1 ... 1800
2
Time that the Sunny Boy wait until it disconnects
from the grid.
Vac-Min *
%
0 ... 50
12
Lower (Vac-Min) and upper (Vac-Max) limit of
allowable AC voltage. Default value is optimal
for installations < 30 kW.
Vac-Max *
%
0 ... 20
10
Vac-Min-Fast *
%
0 ... 50
50
Lower and upper limits of allowable AC
voltage for fast disconnection. Default value is
optimal for installations < 30 kW.
Vac-Max-Fast *
%
0 ... 20
20
Vac-Min-Recnct*
%
0 ... 50
11.7
Values are used to calculate the lower and
upper limits to reconnect to the grid after a grid
failure
Vac-Max-Recnct
%
0 ... 20
5.83
Vconst-Setval
V
75 ... 330
275
PV Setpoint voltage for constant voltage
operation. These parameters only are
important in case the parameter „Operating
Mode“ is set to „V-const“.
Vpv-Start
V
75 ... 150
95
Voltage where the Sunny Boy starts connecting
to the grid.
Name
Unit
Range
Default
Description
Summary of Contents for Sunny Boy SB 700U
Page 1: ...Sunny Boy SB 700U Installation Guide Version 1 1 SB700U 11 SE3207 TBE SB07U...
Page 2: ...ii SMA America SB700U 11 SE3207...
Page 14: ...1 6 SMA America SB700U 11 SE3207...
Page 16: ...2 2 SMA AmericaSB700U 11 SE3207...
Page 24: ...3 8 SMA America SB700U 11 SE3207 11 Verify that the Sunny Boy 700U is firmly mounted in place...
Page 46: ...4 22 SMA America SB700U 11 SE3207...
Page 50: ...6 2 SMA America SB700U 11 SE3207 Figure 6 1 The Sunny Boy LED Status Indicator...
Page 84: ...8 6 SMA America SB700U 11 SE3207...
Page 85: ......