6-24
SMA America
SB700U-11:SE3207
The following parameters appear in parameter list but connot be modified:
Table 6-4
Name
Unit
Range
Default
Description
Plimit
W
600
600
Upper limit of AC output power
SMA-SN
Serial Number of the Sunny Boy
Software-BFR
Firmware version of the operation control unit
(BFR)
Software-SRR
Firmware version of the current control unit (SRR)
Operating Parameters of the Sunny Boy 700U; 100 ... 200 V DC (fixed)
Table 6-5 Operating Parameters of the Sunny Boy 700U; 125 - 250 V DC (changeable)
Name
Unit
Range
Default
Description
AntiIsland-Ampl*
deg
0 ... 10
4
Amplification of the AntiIsland process
AntiIsland-Freq*
mHz
0 ... 2000
500
Repitition rate of the AntiIsland process
CO2-Fact
lbs/
kWh
0 ... 2
1.7
The Sunny Boy evaluates the yield and
indicates the approximate CO2 emission
avoided by your Sunny Boy. The amount of
CO2 avoided is computed according to the
kWh produced (E-total) multiplied by the factor
defined in the parameter „CO2“.
Default
USA/UL1741/
2005;
OFF_GRID;
ADJUSTED
USA/
UL1741/
2005
Used for adjusting the parameters country
specific settings
Note: After changing one of the parameters
marked with * the parameter „Default“
changes to „adjusted“ automatically.
E-Total
kWh
0 ... 200000
Total energy yield (E_Total) of the inverter.
Changing the value can be necessary when a
Sunny Boy is exchanged and you wish to match
the previously acquired data
Fac-Delta- *
Hz
0.2 ... 3
0.69
Maximum allowable frequency above (Fac-
Delta+) and below (Fac-Delta-) 60 Hz. Default
value is optimal for installations < 30 kW.
Fac-Delta+ *
Hz
0 ... 4.5
0.49
Fac-MinTripTime*
s
0.16 ... 300
0.16
Utility interconnection frequency trip time.
Default value is optimal for installations < 30
kW.
h-Total
h
0 ... 200000
Total operating hours (h_Total) of the inverter.
Changing the value can be necessary when a
Sunny Boy is exchanged and you wish to match
the previously acquired data
Summary of Contents for Sunny Boy SB 700U
Page 1: ...Sunny Boy SB 700U Installation Guide Version 1 1 SB700U 11 SE3207 TBE SB07U...
Page 2: ...ii SMA America SB700U 11 SE3207...
Page 14: ...1 6 SMA America SB700U 11 SE3207...
Page 16: ...2 2 SMA AmericaSB700U 11 SE3207...
Page 24: ...3 8 SMA America SB700U 11 SE3207 11 Verify that the Sunny Boy 700U is firmly mounted in place...
Page 46: ...4 22 SMA America SB700U 11 SE3207...
Page 50: ...6 2 SMA America SB700U 11 SE3207 Figure 6 1 The Sunny Boy LED Status Indicator...
Page 84: ...8 6 SMA America SB700U 11 SE3207...
Page 85: ......