SB700U-11:SE3207
SMA America
7-3
Error messages
In case of an error, the Sunny Boy 700U generates the error code according to the
operating mode and the detected error.
Error Code
Description
Error Type
Bfr-Srr
Communication between micro-controllers is failing
Error
EarthCur-
Max-Bfr
BFR-earth current between PV+ and GND is out of tolera-
ble range
Error
EarthCur-
Max-Srr
SRR-earth current between PV+ and GND is out of tolera-
ble range
Error
EEPROM
Transition failure during reading or writing of data EE-
PROM, the data is not essential for safe operation - this fail-
ure does not effect performance.
Error
EEPROM p
Data EEPROM defective, device is set to permanent dis-
able due to the fact that the data loss affects important func-
tions of the inverter. Contact SMA.
Error
EeRestore
Internal failure
Error
Fac-Bfr
Fac-Srr
The AC grid frequency is exceeding the allowable range.
(„Bfr“ or „Srr“ is an internal message and is not important
to the user.) The Sunny Boy assumes that the public grid is
down and disconnects from the grid in order to avoid is-
landing.
Check the grid frequency and the grid cable connection in
the Sunny Boy enclosure. If the grid frequency is out of
range due to your local grid conditions contact the utility
company and ask, if it is permissable to change the grid
monitoring parameters of the inverter. Contact SMA about
how to change the grid monitoring parameters of your Sun-
ny Boy. If the grid frequency is within the tolerable range
and you still observe the failure message „Fac-Bfr“ or „Fac-
Srr“ contact SMA.
Disturbance
GFDI Fuse
Open
The GFDI-Fuse is defective or open
Error
Imax
Overcurrent on the AC side. This failure code is indicated
in case the current to the AC grid exceeds the specification.
This may happen in case of harmfull interference on the
grid. If you observe „F-Imax“ often, check your grid. For as-
sistance contact SMA.
Disturbance
Summary of Contents for Sunny Boy SB 700U
Page 1: ...Sunny Boy SB 700U Installation Guide Version 1 1 SB700U 11 SE3207 TBE SB07U...
Page 2: ...ii SMA America SB700U 11 SE3207...
Page 14: ...1 6 SMA America SB700U 11 SE3207...
Page 16: ...2 2 SMA AmericaSB700U 11 SE3207...
Page 24: ...3 8 SMA America SB700U 11 SE3207 11 Verify that the Sunny Boy 700U is firmly mounted in place...
Page 46: ...4 22 SMA America SB700U 11 SE3207...
Page 50: ...6 2 SMA America SB700U 11 SE3207 Figure 6 1 The Sunny Boy LED Status Indicator...
Page 84: ...8 6 SMA America SB700U 11 SE3207...
Page 85: ......