Additionally required material (not included in the scope of delivery):
☐ Distribution board with required electric equipment
☐ Two electrical current strength transducers (mechanical and electrical characteristics of the
selected electrical current strength transducers must be in accordance with the installation on
site)
☐ One router for the connection to the Internet. SMA Solar Technology AG recommends using
an Internet flat rate.
☐ One switch
☐ Network cable
☐ Data cable of battery
Switch requirements:
☐ At least 5 Ethernet connections must be available
☐ The switch must be permeable for broad and multicasts
☐ Do not use an IGMP Snooping Switch as per RFC 4541
Router requirements:
☐ DHCP should be supported (if possible with MAC address binding). If DHCP is not supported,
an IP from the address range of the router must be assigned manually to each device.
☐ TCP ports 123, 443 and 9524 must be authorized for outgoing connections.
☐ Fast Ethernet with 100 Mbit/s data transfer rate
☐ IGMP protocol version 2 or version 3 (IGMPv2 or IGMPv3) must be supported.
☐ The IPv4 protocol must be used at least in the internal network. The IPv6 protocol may be
active in parallel.
Network cable requirements:
The cable length and quality affect the quality of the signal. Observe the following cable
requirements.
☐ Cable type: 100BaseTx
☐ Cable category: minimum CAT5e
☐ Plug type: RJ45 of Cat5, Cat5e or higher
☐ Shielding: SF/UTP, S/UTP, SF/FTP or S/FTP
☐ Number of insulated conductor pairs and insulated conductor cross-section: at least 2 x 2 x
0.22 mm²
☐ Maximum cable length between two nodes when using patch cables: 50 m (164 ft)
☐ Maximum cable length between two nodes when using installation cables: 100 m (328 ft)
☐ UV-resistant for outdoor use.