Sunny Boy 1800U
Installation and Operator’s Manual
SB2500U-11:NE
-
13
-
SMA Regelsysteme GmbH
WARNING: All electrical installations shall be done in accordance
with all local electrical codes and the National Electrical Code (NEC),
ANSI/NFPA 70. Use no. 14 AWG, minimum 90°C (194°F), copper wire
for all connections with the Sunny Boy. Voltage drop and other con-
siderations may dictate that larger wire sizes be used.
The AC-grid and the input from the DC disconnect enclosure are connected to the in-
verter inside the case. Cables with wire sizes up to 10 AWG (5.26 mm
2
) are accepted by
the AC- and DC-terminals on the printed circuit board.
WARNING: The connection of the Sunny Boy to the DC voltage from
the PV string and the AC voltage of the utility must be done in the
order described here. This ensures that the disconnecting of con-
tacts as well as hazardous voltages during the installation are
avoided.
•
Connect the Sunny Boy to the electricity grid
•
Connect the PV strings to the DC disconnect enclosure
•
Connect the DC disconnect enclosure to the Sunny Boy
•
Connect the utility by switching all breakers ON
To disconnect the Sunny Boy from the system, first turn all breakers and switches OFF.
Then disconnect the various conductors in the reverse order listed above.