Sunny Boy 1800U
Installation and Operator’s Manual
SB2500U-11:NE
-
14
-
SMA Regelsysteme GmbH
2.3.1 Preparation of the electric connection
Remove all screws (1-4, size M5 (see Fig. 2.6)) and take off the lid. When removing
these screws, be sure to save the special lock washers and reinstall them to properly
ground the front panel.
Fig. 2.6
:
Front view of the Sunny Boy 1800U
You now have the opened Sunny Boy in front of you (see Fig. 2.7) and can see the posi-
tion of components and clamps relevant for you. You will find:
•
The internal grid fuse
WARNING: A defective grid fuse has to be replaced only with a UR
fuse of 20AMP / 250V AC in order for continued protection against
risk of fire.
•
The control system board with the socket for the Piggy Back board for the com-
munication
•
Terminal for the AC-connection
•
Terminals for the DC-connection
1
2
3
4