Sunny Boy 1800U
Installation and Operator’s Manual
SB2500U-11:NE
-
43
-
SMA Regelsysteme GmbH
4.7 Measurement Precision
Any kind of measurement always depends on the accuracy. The reproduc
i
bility of the measure-
ment values is conceived for an ambient temperature of 77°F (25 °C). Other temperatures must
be evaluated with respect to the inaccuracy resulting from these different temperatures.
[Unit]
Range
Resolution
Maximal
failure
Display
Measurement
ϑ
U
=+77°F
Input voltage
U
PV
[V]
0...650 V
1 V
1,12 V
±2%
Input current
I
PV
[mA]
0...12000 mA
1 mA
12 mA
±4%
grid voltage
U
AC
[V]
90...150 V
1 V
0,3 V
±1%
grid current
I
AC
[mA]
0...15800 mA
1 mA
30 mA
±2%
grid frequency
f
AC
[Hz]
55.5...64.5 Hz
0,01 Hz
0,01 Hz
±0,1%
output power
P
AC
[W]
0...2500 W
1 W
1 W
±3%
energy yield
E [kWh]
0...4,29* 10
9
Wmin
1 Wmin
20 Wmin
±3%
operating hours
h [h]
0...4,29*10
9
s
1 s
0,67
µ
s
±0,1%
Table 4.1:
Measurement accuracy of the
Sunny Boy