6.2 Status Messages
The inverters can be in various operating modes. These are displayed as status messages which can
vary according to the method of communication.
Vfan
Fan supply voltage
Vpv
PV input voltage
Vpv-Setpoint
PV target voltage
Message
Description and corrective measure
Balanced
The Sunny BoyBoy has disconnected from the grid, or is limiting its output to
6 kW (adustable with parameter PowerBalMax) over a 10-minute average. The
Sunny Boy is part of a three-phase system equipped with two further Sunny Boys
and the SMA Power Balancer to avoid unbalanced load. The "Balanced" message
is displayed for the following reasons:
Case 1:
The operating parameter "PowerBalancer" is set to "PhaseGuard". One of the three
Sunny Boy inverters in this system has indicated a grid fault and disconnected from
the grid. Consequently, the other two Sunny Boy inverters also disconnect from the
grid to avoid an unbalanced load, and send the message "Balanced".
Case 2:
The operating parameter "PowerBalancer" is set to "PowerGuard". One of the
3 Sunny Boys in this system has detected a device or grid fault and disconnected
from the grid. The two remaining Sunny Boys reduce their output over a 10-minute
average to 6 kW (adustable with parameter PowerBalMax) in order to prevent an
unbalanced load.
Case 3:
The operating parameter "PowerBalancer" is set to "FaultGuard". One of the 3
Sunny Boys in this system has indicated a device or grid fault and disconnected
from the grid.
When grid failure occurs, the other two Sunny Boys also disconnect from the grid
to prevent an unbalanced load, and send the message "Balanced".
In the event of a device fault, the fault message is sent to the other two devices with
a time lapse of 5 min. After the 5 min. have passed, the other two devices
disconnect from the grid and send the message "Balanced".