Operating modes
User Manual
SB_CL_US-BUS094410
15
3.1.4 The green LED is blinking slowly
Waiting, Grid Monitoring
The inverter has determined that there is enough voltage
from the array to operate and is checking the condition of
the grid prior to connecting to it.
If the inverter fails to connect to the utility grid 3 times in
a row, it will wait 10 min. before the next attempt.
In case of a grid failure, the Sunny Boy waits 5 min.
before it tries to reconnect to the grid.
3.1.5 The green LED is continuously on
Feeding operation
The inverter is feeding the utility grid in either “MPP” or
“Constant Voltage” mode.
“MPP” Mode: The Sunny Boy adjusts the voltage and
current from the PV array to obtain the greatest PV output
power.
“Constant Voltage” Mode: The voltage from the PV array
has been set to a fixed value. This value is set by using the
Sunny Boy Control or the Sunny Data software (the parameter name is “V-Const”). This mode is
typically used for fuel cell or micro-hydro applications.
3.1.6 The green LED goes out briefly
Derating
The Sunny Boy is designed to operate at full rated power
up to 113 °F (45 °C) ambient temperature. The inverter
will continue to operate beyond 113 °C (45 °C) and
will derate as required to maintain a safe internal
component temperature. Unnecessary derating can be
caused by blocked fan intakes. For this reason the fan
intakes must be inspected in regular intervals and
cleaned if necessary.