4 Disconnecting and Reconnecting
SMA Solar Technology AG
Maintenance Manual
SCCPXT-E7-WA-en-37
26
4
Disconnecting and Reconnecting
4.1
Safety When Disconnecting and Reconnecting Voltage Sources
DANGER
Danger to life from electric shock due to live voltage
High voltages are present in the live components of the product. Touching live components results in death or
serious injury due to electric shock.
• Wear suitable personal protective equipment for all work on the product.
• Do not touch any live components.
• Observe all warning messages on the product and in the documentation.
• Observe all safety information of the module manufacturer.
• After switching off the inverter, wait at least 15 minutes before opening it to allow the capacitors to discharge
completely (see Section 4.2, page 26).
DANGER
Danger to life due to electric shock in case of a ground fault
If there is a ground fault, components that are supposedly grounded may in fact be live. Touching live parts will
result in death or serious injury due to electric shock.
CAUTION
Risk of burns due to hot components
Some components of the product can get very hot during operation. Touching these components can cause burns.
• Observe the warnings on all components.
• During operation, do not touch any components marked with such warnings.
• After switching off the product, wait until any hot components have cooled down sufficiently.
• Wear suitable personal protective equipment for all work on the product.
4.2
Disconnecting the Inverter
4.2.1
Switching off the Inverter
1. Turn the key switch to
Stop
.
2. Remove the key. This will protect the inverter from inadvertent reconnection.
3. Wait 15 minutes before opening the doors. This allows the inverter capacitors to discharge.
4.2.2
Disconnecting the DC Side
1. Switch off the inverter (see Section 4.2.1, page 26).
2. Disconnect all poles of the DC voltage in the DC main distribution or DC subdistribution (see documentation of the
main or subdistribution).
3. Ensure that the DC switchgear in the inverter is open.
4. Ensure that no voltage is present on the load side of the DC switchgear.
5. Cover or isolate any adjacent live components.
6. Remove the protective covers over the fuses.
7. Remove all fuses and disconnection blades from all fuse holders of the inverters. Use an LV/HRC fuse extractor.