6 Maintenance
SMA Solar Technology AG
Maintenance Manual
SCCPXT-E7-WA-en-37
56
6.4.2.6
Checking the Seals
Figure 17: Section drawing with top view of a door seal (example)
Position
Designation
A
Seal
B
Side panel
C
Sealing area
D
Hinge
E
Door
F
Frame construction
Required maintenance material (not included in the scope of delivery):
☐ A suitable water-free, heat-resistant lubricant
☐ Talcum, petroleum jelly or wax for maintaining the seals
DANGER
Danger to life due to electric shock or electric arc if live components are touched
• Switch off the inverter and wait at least 15 minutes before opening it to allow the capacitors to discharge
completely.
• Disconnect the inverter (see Section 4, page 26).
Procedure:
1. Check whether the seals in the sealing area show any damage.
If seals are damaged, contact us (see Section 9 "Contact", page 68).
2. Apply talcum, petroleum jelly or wax to seals. This will prevent frost damage.
3. After removing the side panels: check whether the side panel seals display any damage in the sealing area.
If seals are damaged, contact us (see Section 9 "Contact", page 68).
6.4.2.7
Checking the Latches, Door Stops and Hinges
Required maintenance material (not included in the scope of delivery):
☐ A suitable, water-free and heat-resistant lubricant, e.g. WD40
☐ Non-greasing antifreeze agent, e.g. PS88
Summary of Contents for SUNNY CENTRAL 1000CP XT
Page 70: ...www SMA Solar com...