5 Troubleshooting
SMA Solar Technology AG
Maintenance Manual
37
SCCPXT-E7-WA-en-37
5.4.5
Error Numbers 6xxx to 9xxx - Disturbance on the Inverter
Error no. Explanation
Inverter behavior
Corrective measures
S1
S2
R
6002
Calibration data cannot be
loaded.
Q
Q
‒
• Contact the SMA Service Line.
6113
Data block cannot be loaded from
EEPROM or channel list has
changed (e.g. after firmware up-
date).
W
W
‒
• Contact the SMA Service Line.
6115
Setting of hardware thresholds on
D/A converters is not possible.
5 min
5 min
x
• Contact the SMA Service Line.
6116
Real-time clock has not initialized.
W
W
‒
• Contact the SMA Service Line.
6117
Device address not recognized.
5 min
5 min
x
• Contact the SMA Service Line.
6119
Data structure for communication
between operation control unit
and digital signal processor is in-
valid.
5 min
5 min
x
• Contact the SMA Service Line.
6120
Watchdog tripping error
30 s
W
‒
• Contact the SMA Service Line.
6121
No response from watchdog
30 s
W
‒
• Contact the SMA Service Line.
6122
Ten internal monitoring errors have
occurred in succession.
W
5 min
‒
• Contact the SMA Service Line.
6128
General error
5 min
5 min
x
• Contact the SMA Service Line.
6404
Overcurrent at line conductor L1,
L2 or L3
C
Q
x
• Contact the SMA Service Line.
6405
Overvoltage in the DC link of the
inverter bridge
30 s
5 min
‒
• Contact the SMA Service Line.
6410
24 V supply voltage is invalid.
5 min
5 min
x
• Contact the SMA Service Line.
6417
15 V supply voltage is invalid.
5 min
5 min
x
• Contact the SMA Service Line.
6418
Overtemperature of the inverter
bridge
5 min
15
min
‒
• Contact the SMA Service Line.
6422
Inverter bridge in undefined state
30 s
5 min
‒
• Contact the SMA Service Line.
6423
Overtemperature in the switch
cabinet
5 min
30
min
‒
• Contact the SMA Service Line.
6425
Synchronization error with utility
grid
30 s
5 min
x
• Contact the SMA Service Line.
6427
Sensor error of DC voltage mea-
surement
30 s
C
‒
• Contact the SMA Service Line.
6440
The MV transformer is no longer
hermetically sealed.
30 s
5 min
‒
• Check the MV transformer.
Summary of Contents for SUNNY CENTRAL 1000CP XT