6 Maintenance
SMA Solar Technology AG
Maintenance Manual
57
SCCPXT-E7-WA-en-37
DANGER
Danger to life due to electric shock or electric arc if live components are touched
• Switch off the inverter and wait at least 15 minutes before opening it to allow the capacitors to discharge
completely.
• Disconnect the inverter (see Section 4, page 26).
Procedure:
1. Check whether the doors latch easily. Open and close the doors several times.
If the doors do not latch easily, lubricate all moving parts of the latch.
2. Check whether the stops hold the doors in place.
If the doors cannot be arrested, lubricate the door stops.
3. Check whether the door hinges move easily.
If the door hinges do not move easily, apply lubricant.
4. Lubricate all moving parts and movement points.
5. Tighten any loose screws with the appropriate torque.
6. If the inverter is installed in regions where below-freezing temperatures occur, apply the non-greasing antifreeze to
the profile cylinder of the door lock and the key switch in order to protect them from icing up.
6.4.2.8
Checking the Inverter Surface
Required maintenance material (not included in the scope of delivery):
☐ Abrasive cloth
☐ Degreaser
☐ Use touch-up sticks, paint brushes, cans of spray paint or, alternatively, 2K-PUR acrylic paint in the appropriate
RAL color to repair small-area surface damage. Observe the relevant instructions of the paint manufacturer.
☐ Use touch-up paint or alternatively 2K-PUR acrylic paint in the appropriate RAL color to repair large-area surface
damage. Observe the relevant instructions of the paint manufacturer.
☐ Use zinc plating with thick-layer passivation to repair the damage on the zinc-plated steel frame in the base area,
e.g. LZ-09. Observe the relevant instructions of the manufacturer.
Position
RAL color
Color
Roof
RAL 7004
Signal gray
Base
RAL 7004
Signal gray
Enclosure
RAL 9016
Traffic white
DANGER
Danger to life due to electric shock or electric arc if live components are touched
• Switch off the inverter and wait at least 15 minutes before opening it to allow the capacitors to discharge
completely.
• Disconnect the inverter (see Section 4, page 26).
Procedure:
1. Remove dirt.