6 Maintenance
SMA Solar Technology AG
Maintenance Manual
59
SCCPXT-E7-WA-en-37
NOTICE
Damage to bolted connections through overtightening
If the permitted torques are exceeded, bolted connections can be damaged. In this case, fault-free operation of the
inverter is no longer ensured.
• Only tighten loose bolted connections to the prescribed torque. Torque specifications are indicated in the
circuit diagram of the inverter. If there is any information missing, contact (see Section 9 "Contact", page 68).
Procedure:
1. Check that the bolted connections of all assemblies are securely in place.
If bolted connections are loose, tighten them using a torque wrench.
2. Check whether all bolted connections of the power cabling are securely in place.
If bolted connections are loose, tighten them using a torque wrench.
3. Check the insulation and connections for any discoloration or change in appearance.
If insulation and connections are discolored or changed, contact us (see Section 9 "Contact", page 68).
4. Check the bolted connections for damage and contact elements for corrosion.
If bolted connections are damaged or contact elements corroded, replace them.
6.4.2.11 Checking the Labels
Inverter labels can be ordered from us as a complete set.
SMA order number
Languages included
3F1-050-001-001
en, de, es, fr
3F1-050-002-001
en, el, it
3F1-050-003-001
en, ja, ko, zh
3F1-050-004-001
en, ro, tr