6 Maintenance
SMA Solar Technology AG
Maintenance Manual
61
SCCPXT-E7-WA-en-37
Position
Material number
Designation
G
86-0043553
Risk of lethal electric shock due to active power source
H
86-003307
5 Safety rules
I
86-1086701026
The negative pole of the PV generator is grounded in the inverter.
86-1086701027
The positive pole of the PV generator is grounded in the inverter.
K
86-003304
Unintended tripping due to modified settings.
L
86-003306
Plant protected by conductors.
M
86-003305
Incorrect connection leads to destruction of the device.
N
86-1086701023
Risk of lethal electric shock due to active power source
O
86-0099
Position of grounding
P
86-1086701024
Danger of burn injury due to hot components below the cover.
Q
86-10867153
Risk of electrical shock even when the device is disconnected.
DANGER
Danger to life due to electric shock or electric arc if live components are touched
• Switch off the inverter and wait at least 15 minutes before opening it to allow the capacitors to discharge
completely.
• Disconnect the inverter (see Section 4, page 26).
Procedure:
• Check whether any warning message or label is damaged or missing.
Replace any warning messages and labels which are missing or illegible. If necessary, you can order labels as a
complete set. Contact us (see Section 9, page 68).
6.5
Repair Work
6.5.1
Reading off the Replacement Interval Meter
1. Log into the user interface as an installer (see Section 7.4.1, page 66).
2. Select
Data > Devices
.
3. Select the desired device from the list.
4. Select the tab
Instantaneous values
.
5. If the instantaneous value
CntGfdiSw
exceeds 7000, replace the Remote GFDI (see Section 9 "Contact",
6. If the error message
7714
appears on the touch display, replace the GFDI (see Section 9 "Contact", page 68).