ChkGdVtgMax
288 ... 332,4 Vrms 332,4 Vrms
Maximum voltage for Sunny Central
operation.
If the voltage exceeds the value defined
in ChkGdVtgMax, the Sunny Central
shuts down immediately.
ChkGdVtgMin
138,5 ... 265,9 Hz 138,5 Hz
Minimum voltage for Sunny Central
operation.
If the voltage drops below the value
defined at ChkGdVtgMin, the Sunny
Central shuts down immediately.
ChkGnFrqLo
Sunny Central operation with a
generator.
More information on parameter settings
and operating the Sunny Central with a
generator can be obtained from SMA
America.
ChkGnFrqLoT
ChkGnFrqMax
ChkGnFrqMin
ChkGnVtgHi
ChkGnVtgLo
ChkGnVtgMax
ChkGnVtgMin
Dt
yyyymmdd
Current Date.
Here you can set the current date.
Ofs_E-Total
0 ... 214748364
kWh
0 kWh
The Sunny Central's total energy yield
Changing the Ofs_E_Total parameter
may be necessary if you exchange the
computer assembly (BFR) of the Sunny
Central and want to transfer the data
from the old device.
Ofs_h-On
0 ... 2147483 h
0 h
The Sunny Central's total number of
hours of operation
Changing the Ofs_h_On parameter may
be necessary if you exchange the
computer assembly (BFR) of the Sunny
Central and want to transfer the data
from the old device.
Parameter Name Range
Default
Parameter Description