12 Parameters
SMA Solar Technology AG
100
SCCP-JP-BA-A4-en-12
User Manual
12.1.3 Grid Support
Name
Description
Value/range Explanation
Default value
Slope of the FRT characteristic
curve in accordance with the
System Service Ordinance
SDLWindV in case of overvoltage
0 to 10
Values between
0 and 2 are
recommended.
For other values,
contact the SMA
Service Line.
2
FRT2ArGraNomLo*
Slope of the FRT characteristic
curve in accordance with the
System Service Ordinance
SDLWindV in case of undervoltage
0 to 10
‒
2
Scaling of K factor for full dynamic
grid support
0 to 10
‒
2
Upper limit of voltage deadband
0% to 100%
‒
10%
Lower limit of voltage deadband
− 100% to 0% ‒
− 10%
FRTEna*
* To view or change this parameter, you must enter the installer password.
Enables dynamic grid support
Off
Deactivated
On
On
Activated
FRTMod**
** You can only view this parameter after entering the installer password.
Dynamic grid support mode
FRT_BDEW
Dynamic grid
support in
accordance with
BDEW directives
FRT_SDLWindV
FRT_Partial
Pulse block in the
event of FRT
FRT_SDLWindV Dynamic grid
support in
accordance with
SDLWindV
Deactivation delay for dynamic
grid support
0 ms to 1,000
ms
‒
500 ms
Enables islanding detection
Off
Deactivated
On
On
Activated
TrfVolExlHi***
*** To change this parameter, you must enter the installer password.
Line-to-line voltage on overvoltage
side of external transformer
1 V to
70,000 V
‒
20,000 V
Line-to-line voltage on undervoltage
side of external transformer
1 V to 500 V
SC 500CP-JP
205 V
SC 630CP-JP
315 V
SC 800CP-JP
360 V