SMA Solar Technology AG
12 Parameters
User Manual
SCCP-JP-BA-A4-en-12
101
12.1.4 Insulation Monitoring
12.1.5 Internal Device Values
Name
Description
Value/range Explanation
Default
value
IsoErrIgn*
* To view or change this parameter, you must enter the installer password.
Enables insulation error
detection, continued operation
in the event of insulation error
Off
Deactivated
Off
On
Activated
Run
Error is only ignored if the
inverter is in feed-in operation
RemMntSvc
Deactivates PV array grounding.
Off
Deactivated
Off
On
Activated
RisoCtlWarn
Warning threshold for insulation
monitoring device iso-PV1685
0 kΩ to 50 kΩ ‒
45 kΩ
PvVtgRisoStart
Start voltage of insulation
measurement
0 V to 1,200 V SC 500CP-JP
410 V
SC 630CP-JP
610 V
SC 800CP-JP
760 V
PvVtgRisoDif
Differential voltage to
PvVtgStrLevMin
for switching
from insulation measurement to
feed-in operation
− 250 V to
+250 V
‒
0 V
IsoDev*
Selection of insulation
monitoring device
isoPV3
‒
isoPV3
isoPV1685
‒
Name
Description
Value/range Explanation
Default value
Ackn
Acknowledges errors in Sunny Central
Ackn
Acknowledge
errors
−
MMC/SD memory card function
ForcedWrite
Terminate SD
memory card
‒
StoFailHis
Write fault
memory to SD
memory card
Meter reset
h-Cnt
Operating hours
meter
‒
E-Cnt
Energy meter
CntFanHs
All fan runtime
meters
CntFanCab2
Fan runtime meter
CntHtCab2
Fan runtime meter
CntrySet*
Selection of valid power frequency
This parameter can only be changed in
the operating state "Stop".
J50
For 50 Hz grid
‒
J60
For 60 Hz grid