SMA Solar Technology AG
10 Troubleshooting
User Manual
SCCP-JP-BA-A4-en-12
81
10.4.5 Error Numbers 60xx to 90xx - Disturbance on the Sunny Central
Error no.
Explanation
Behavior of the
Sunny Central
Corrective measures
S 1
S 2
R
6002
Calibration data cannot be loaded.
Q
Q
‒
• Contact the SMA Service Line.
6113
Data block cannot be loaded from
EEPROM or channel list has
changed (e.g. after firmware
update)
W
W
‒
6115
Setting of hardware thresholds on
D/A converters not possible.
5 min
5 min
x
6116
Real-time clock not initialized.
W
W
‒
6117
Device address not recognized.
5 min
5 min
x
6118
Parameter file invalid.
W
W
‒
6119
Data structure for communication
between operation control unit and
digital signal processor invalid.
5 min
5 min
x
6120
Watchdog tripping error
30 s
W
‒
6121
No response from watchdog
30 s
W
‒
6122
Ten internal monitoring errors have
occurred in succession.
W
5 min
‒
6123
Software runtime error
W
W
‒
6128
Internal runtime error
5 min
5 min
x
6404
Overcurrent on line conductor L1,
L2 or L3
C
Q
x
6405
Overvoltage in the DC link of the
inverter bridge
30 s
5 min
‒
6410
24 V voltage supply invalid
5 min
5 min
x
6417
15 V voltage supply invalid
5 min
5 min
x
6418
Overtemperature on the inverter
bridge detected
5 min
15 min
‒
6422
Inverter bridge in undefined state
30 s
5 min
‒
6423
Overtemperature detected in the
switch cabinet
5 min
30 min
‒
6425
Synchronization error with
utility grid
30 s
5 min
x
6427
Sensor error of DC voltage
measurement
30 s
C
‒
6440
Hermetic protection of transformer
no longer assured
30 s
5 min
‒
• Check external transformer.