10 Troubleshooting
SMA Solar Technology AG
84
SCCP-JP-BA-A4-en-12
User Manual
8704
External active and reactive power
setpoints invalid
W
W
‒
• Contact the SMA Service Line.
9000
Power electronics self-test running
This message disappears once the
self-test is complete.
W
W
‒
9008
Doors have been opened during
operation.
30 s
1 min
x
9009
Fast stop has been manually
tripped.
30 s
30 s
‒
• Eliminate error and switch fast
stop back on.
9013
This is a grid stability shutdown (see
Section 3.8.7). The error is reset by
a signal from the grid operator or
from the safety system of the grid
interconnection point.
30 s
30 s
‒
9019
Defective fast stop
30 s
Q
‒
• Ensure that the fast stop is
correctly connected.
Error no.
Explanation
Behavior of the
Sunny Central
Corrective measures
S 1
S 2