SMA Solar Technology AG
12 Parameters
User Manual
SCCP-JP-BA-A4-en-12
91
Gradient of power
reduction
1%/Hz to 100%/Hz
‒
40%/Hz
PFAbsMin*
Limitation of the
displacement power
factor cos φ
0.5 to 1
The parameter should not
fall below 0.8 in normal
operation.
0.9
PF-PF
Displacement power
factor cos φ
The lower limit is
defined by the
parameter
PFAbsMin
.
0.5 to 1
The parameter should not
fall below 0.8 in normal
operation.
1
PF-PFExt
Excitation of the
displacement power
factor cos φ
OvExt
Lagging
OvExt
UnExt
Leading
Displacement power
factor cos φ at
characteristic curve
point 1
The lower limit is
defined by the
parameter
PFAbsMin
.
0.5 to 1
The parameter should not
fall below 0.8 in normal
operation.
0.9
PF-PFExtStr**
Excitation of the
displacement power
factor cos φ at
characteristic curve
point 1
OvExt
Lagging
OvExt
UnExt
Leading
Displacement power
factor cos φ at
characteristic curve
point 2
The lower limit is
defined by the
parameter
PFAbsMin
.
0.5 to 1
The parameter should not
fall below 0.8 in normal
operation.
0.9
Excitation of the
displacement power
factor cos φ at
characteristic curve
point 2
OvExt
Lagging
OvExt
UnExt
Leading
Specification of feed-in
power in % at
characteristic curve
point 1
0% to 90%
‒
0%
Specification of feed-in
power in % at
characteristic curve
point 2
10% to 100%
‒
100%
Name
Description
Value/range
Explanation
Default
value