12 Parameters
SMA Solar Technology AG
92
SCCP-JP-BA-A4-en-12
User Manual
P-VtgGraNom
Active power gradient
for voltage-dependent
active power limitation
0.017%/s to
100.000%/s
‒
0.166%/s
P-VtgEna
Activation of
voltage-dependent
active power limitation
Off
Deactivated
Off
On
Activated
P-VtgNomP1
Voltage at point 1
100% to 120%
‒
110%
P-VtgNomP2
Voltage at point 2
90% to 120%
‒
100%
P-VtgAtMin
Minimum active power
for voltage-dependent
active power limitation
0% to 100%
‒
20%
PwrApLimitPrio*** Prioritization of reactive
power or active power
PrioPwrRt
Prioritization of reactive
power
PrioPwrRt
PrioPwrAt
Prioritization of active
power
P-WSubVal
Proxy value for active
power limitation outside
of normal feed-in
operation in the event of
communication failure
0 kW to 1,000 kW
SC 500CP-JP
500 kW
SC 630CP-JP
700 kW
SC 800CP-JP
880 kW
PF-PFSubVal
Proxy value for cos φ
outside of normal
feed-in operation in the
event of communication
failure
0.5 to 1
The value 0.5 cannot be
reached in normal
operation.
1
PF-PFExtSubVal
Proxy value for
excitation type in the
event of communication
disturbance
OvExt
Lagging
OvExt
UnExt
Leading
P-WSubValRun
Proxy value for the
active power limitation
during feed-in operation
in the event of
communication
disturbance
0 kW to 1,000 kW
SC 500CP-JP
500 kW
SC 630CP-JP
700 kW
SC 800CP-JP
880 kW
PF-PFSubValRun
Proxy value cos φ in
normal feed-in
operation in the event of
communication
disturbance
0.5 to 1
The parameter should not
fall below 0.8 in normal
operation.
1
PF-PFExtSubValR
Proxy value of the
excitation type during
normal feed-in
operation in the event of
communication
disturbance
OvExt
Lagging
OvExt
UnExt
Leading
Name
Description
Value/range
Explanation
Default
value