SMA Solar Technology AG
12 Parameters
User Manual
SCCP-JP-BA-A4-en-12
93
Power from which the
cos φ(P) characteristic
curve is activated, in %
relative to the nominal
voltage
0% to 110%
‒
0%
PF-WLockOutVtg** Power from which the
cos φ(P) characteristic
curve is deactivated, in
% relative to the
nominal voltage
0% to 110%
‒
0%
PF-WLockTm**
Waiting time for
activating or
deactivating the cos
φ(P) characteristic curve
0 s to 100 s
‒
2 s
PwrMonErrMod
Mode used in the event
of communication
failure
LastVal
Use of last default values
received
LastVal
SubVal
Use of proxy values
PwrMonErrTm
Communication
downtime until proxy
values are used
1 s to 999 s
‒
300 s
Q-EnaTmsVtg**
Activation of line
voltage delay in the
parameter
Q-VarTmsVtg
Off
‒
Off
On
‒
Voltage value from
which the Q(V)
characteristic curve is
activated, in % relative
to the nominal voltage
0% to 100%
‒
0%
Voltage value from
which the Q(V)
characteristic curve is
deactivated, in % based
on the nominal voltage
0% to 100%
‒
0%
Q-VLockInTm**
Waiting time for
activation of Q(V)
characteristic curve
0 s to 100 s
‒
2 s
Waiting time for
deactivation of Q(V)
characteristic curve
0 s to 100 s
‒
2 s
Q-VArGraNom
Reactive power
gradient at a positive
change of nominal
voltage
0%/V to 44.06%/V
SC 500CP-JP
0%/V
0%/V to 31.47%/V
SC 630CP-JP
0%/V to 25.04%/V
SC 800CP-JP
Name
Description
Value/range
Explanation
Default
value