12 Parameters
SMA Solar Technology AG
94
SCCP-JP-BA-A4-en-12
User Manual
Q-VArGraNom
Reactive power
gradient at a negative
change of nominal
voltage
0%/V to 44.06%/V
SC 500CP-JP
0%/V
0%/V to 31.47%/V
SC 630CP-JP
0%/V to 25.04%/V
SC 800CP-JP
Q-VArMod**
Specification of the
reactive power setpoint
mode
Off
Sets reactive power to
0 kVAr and displacement
power factor cos φ to 1
Off
VArCtlCom
Specification of reactive
power via external control
unit, such as the Power
Reducer Box
PFCtlCom
Specification of
displacement power factor
cos φ and excitation of the
displacement power factor
via an external control unit
such as the Power Reducer
Box
VArCnst
Specification of reactive
power in kVAr via the
parameter
Q-VAr
VArCnstNom
Specification of reactive
power in % via the
parameter
Q-VArNom
VArCnstNomAnIn
The reactive power setpoint
is imported via an analog
input.
PFCnst
Manual specification of
displacement power factor
cos φ and excitation of the
displacement power factor
via the parameters
PF-PF
and
PF-PFExt
PFCnstAnIn
Specification of
displacement power factor
cos φ at the analog input
QExlSpnt
via control unit
PFCtlW
Specification of
displacement power factor
cos φ as a function of the
feed-in power
VArCtlVol
Specification of reactive
power as a function of the
line voltage
Name
Description
Value/range
Explanation
Default
value