SMA Solar Technology AG
12 Parameters
User Manual
SCCP-JP-BA-A4-en-12
103
12.2 Sunny Central String-Monitor Controller
PVStrT
Timer: once the specified time has
elapsed, the Sunny Central switches
from the operating state "Grid
monitoring" to the operating state
"Grid monitoring time reached"
1 s to 300 s
‒
90 s
QoDInvCurPv**
Minimum allowed reverse current to
PV array
− 1,600 A to
0 A
‒
− 60 A
Serial number**
Serial number of the Sunny Central
0 to
2147483647
‒
0
SpntRemEna
Remote activation of the system
Stop
Deactivated
Run
Run
Activated
TmSet
Time
0 to 235959
hhmmss
‒
TmZn
Time zone
GMT ‒12:00 to
GMT 12:00
Configurable time
zones
GMT 9:00
VArGra***
Gradient of reactive power change
0%/s to
200%/s
‒
20 %/s
* To view or change this parameter, you must enter the installer password.
** This parameter can only be viewed.
*** To change this parameter, you must enter the installer password.
Name
Description
Value/range
Explanation
Default
value
Serial number
Display of serial number
‒
Value cannot be
changed
−
Firmware
Firmware version of operation
control unit
0 to 255.0
‒
−
Firmware2
Firmware version of digital
signal processor
0 to 255.0
‒
−
Dt
Date entry
20060101 to
20991231
Entered in the format
YYYYMMDD
−
Tm
Time entry
0 to 235959
Entered in the format
HHMMSS
−
TolGr
1
*
Deviation of group
1
currents
from mean value
5% to 100%
Parameter exists for all six
groups.
13%
MoniTmGr
1
On*
Start time for group
1
monitoring
7:00 a.m. to
7:00 p.m.
Parameter exists for all six
groups.
10.00
a.m.
MoniTmGr
1
Stop time for group
1
monitoring
7:00 a.m. to
7:00 p.m.
Parameter exists for all six
groups.
3:00 p.m.
MoniTmGrAllOn*
Start time for monitoring of all
groups
7:00 a.m. to
7:00 p.m.
‒
10:00
a.m.
Stop time for monitoring of all
groups
7:00 a.m. to
7:00 p.m.
‒
3:00 p.m.
Name
Description
Value/range Explanation
Default value